Gas Unit Heaters
A gas unit heater is the workhorse garage heater for shops, pole barns and warehouses. A fan blows warm air across the space from a ceiling-hung cabinet, and a built-in power venter pushes exhaust outside through a 4 in. vent, horizontally through a wall or vertically through the roof. Our unit heaters ship ready for natural gas with the propane conversion kit in the box, and the heat exchanger is covered for 10 years.
To size a garage heater, multiply the garage’s volume in cubic feet by the temperature rise you need and by 0.133 for standard insulation (about 0.17 if it’s uninsulated, 0.10 if it’s well insulated). A 24 x 24 ft two-car garage with 8 ft ceilings is 4,608 cu ft, so warming it from 0°F to 60°F takes about 36,800 BTU/h. Compare that to the heater’s output, which runs from 24,900 to 98,400 BTU/h here, and size up for high ceilings, uninsulated doors or a colder climate. A contractor’s heat-loss calculation gives the exact number.
Vent with standard combustion using room air, or separated combustion using outside air, which is required in repair garages. Every unit needs a gas supply with a drip leg and shut-off, a 115-volt circuit and a 24-volt wall thermostat kept at 50°F or higher. Above 2,000 ft, the input is derated 4% for every 1,000 ft.